一起500 kV斷路器拒動(dòng)故障原因分析及改進(jìn)措施

來(lái)源:電工電氣發(fā)布時(shí)間:2017-02-18 08:18 瀏覽次數(shù):10
一起500 kV斷路器拒動(dòng)故障原因分析及改進(jìn)措施
 
石萬(wàn)里,夏武
(中國(guó)南方電網(wǎng)超高壓輸電公司柳州局,廣西 柳州 545006)
 
    摘 要:介紹了倒閘操作過(guò)程中5051 斷路器分閘不成功事件過(guò)程,通過(guò)對(duì)該故障斷路器進(jìn)行拆分檢查、測(cè)試及分析,指出該斷路器發(fā)生軸承銹蝕導(dǎo)致合閘彈簧未完全釋放,不能給分閘彈簧儲(chǔ)能,是斷路器分閘不成功的主要原因,針對(duì)此類(lèi)斷路器故障并從一次結(jié)構(gòu)、二次信號(hào)回路等方面提出改進(jìn)措施,避免了斷路器拒動(dòng)故障的發(fā)生。
    關(guān)鍵詞:斷路器;拒動(dòng);儲(chǔ)能;改進(jìn)
    中圖分類(lèi)號(hào):TM561     文獻(xiàn)標(biāo)識(shí)碼:A     文章編號(hào):1007-3175(2017)02-0059-04
 
Analysis and Improvement Measures of Refusal-Operation Failure Cause of 500 kV Circuit Breaker
 
SHI Wan-li, XIA Wu
(Liuzhou Bureau of China Southern Power Grid Extra High Voltage Power Transmission Company, Liuzhou 545006, China)
 
    Abstract: Introduction was made to the refusal-operation of 5051 circuit breakers in the process of switching operation. This paper carried out splitting inspection, test and analysis for the malfunction circuit breaker and pointed out that the rusting bearings made the closing spring not completely released in the circuit breaker, which couldn’t store energy for the tripping spring, being the main reason of unsuccessful tripping of the circuit breaker. In allusion to this type of circuit breakers faults, the primary structure and the second signal circuits, this paper proposed improved measures, so as to prevent the circuit breakers refusal-operation from happening.
    Key words: circuit breaker; refusal-operation; stored energy; improvement
 
參考文獻(xiàn)
[1] 宋宇. 斷路器拒動(dòng)故障原因分析及預(yù)防處理措施[J]. 現(xiàn)代制造,2014(30):40-41.
[2] 舒雙焰,趙有鋮,趙曼勇,等.“1.20”安順電廠斷路器拒動(dòng)保護(hù)動(dòng)作分析[J]. 電力系統(tǒng)保護(hù)與控制,2008,36(18):103-107.
[3] Q/CSG 10006—2004 電氣操作導(dǎo)則[S].
[4] Q/CSG 21003—2008 中國(guó)南方電網(wǎng)電力調(diào)度管理規(guī)程[S].
[5] 金長(zhǎng)軍,楊紹露. 淺析防止500 kV斷路器拒動(dòng)的措施[J]. 黑龍江科技信息,2011(30):6.