Suzhou Electric Appliance Research Institute
期刊號(hào): CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁(yè) >> 文章檢索 >> 往年索引

地下低壓配電房通風(fēng)降噪仿真與分析

來(lái)源:電工電氣發(fā)布時(shí)間:2016-04-06 15:06 瀏覽次數(shù):17

地下低壓配電房通風(fēng)降噪仿真與分析 

蔣丹1,鄧海宏2,溫文濤2,王璐2,趙書(shū)濤1 
1 華北電力大學(xué) 電氣與電子工程學(xué)院院,河北 保定 071003;2 佛山電力設(shè)計(jì)院有限公司 
 

摘 要:為合理控制居民區(qū)地下配電房的室內(nèi)溫度,降低機(jī)械通風(fēng)帶來(lái)的環(huán)境噪聲,建立了配電房風(fēng)速場(chǎng)仿真模型并對(duì)其進(jìn)行分析計(jì)算。以某住宅樓地下配電房為例,使用ANSYS13.0軟件對(duì)其中主要熱源——變壓器周?chē)娘L(fēng)速場(chǎng)進(jìn)行模擬與分析。結(jié)果表明:在保證室內(nèi)電氣設(shè)備工作溫度前提下,優(yōu)化計(jì)算通風(fēng)量,通過(guò)電纜溝輔助進(jìn)行機(jī)械排風(fēng),使配電房噪聲由之前的平均值79dB降低到71dB。通過(guò)修改模型參數(shù),可用于其它地下配電房溫度場(chǎng)的模擬與預(yù)測(cè),為前期設(shè)計(jì)提供參考。
關(guān)鍵詞:地下配電房;通風(fēng);降噪;電纜溝;通風(fēng)量
中圖分類(lèi)號(hào):TM641 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1007-3175(2014)12-0021-05


Simulation and Analysis of Ventilation and Noise Reduction in Underground Low-Voltage Power Distribution Room 

JIANG Dan1, DENG Hai-hong2, WEN Wen-tao2, WANG Lu2, ZHAO Shu-tao1 
1 School of Electrical & Electronic Engineering, North China Electric Power University, Baoding 071003, China;2 Foshan Electric Power Design Institute Co., Ltd, Foshan 528200, China 
 

Abstract: In order to control the temperature of residential underground distributing substations reasonably and to reduce environmental noise caused by mechanical ventilation, this paper built up and calculated the simulation model of wind field in distributing substation. Taking certain dwelling house for example, this paper simulated and analyzed the main heat source from the wind field around the main transformer with the software, ANSYS13.0. The simulation results show that under the normal temperature of electrical equipment in the room, the ventilation volume was optimized by machinery exhaustion assisted by cable trench, and the noise level decreased from 79 dB to 71 dB. If the model parameters were modified, the model could be used to predict the temperature field in the same kind of substations, so as to put forward an optimum proposal for noise treatment, and provide more references for preliminary design.
            Key words: underground substations; ventilation; noise reduction; raceway; amount of ventilation


參考文獻(xiàn)
[1] 李明,陳錦棟.城市110 kV室內(nèi)變電站噪聲控制的分析[J].噪聲與振動(dòng)控制,2012,32(1):105-108.
[2] 黃敏均.戶(hù)內(nèi)配電變壓器低頻噪聲監(jiān)測(cè)分析與治理[J].江蘇電機(jī)工程,2011,30(2):55-58. 
[3] 阮國(guó)方,余陸金.戶(hù)內(nèi)變壓器噪聲排放和散熱通風(fēng)的治理[J].湖北電力,2000,24(1):48-50.
[4] 金淋芳.城市全戶(hù)內(nèi)變電站主變壓器室通風(fēng)降噪研究[J].供用電,2010,27(2):39-41.
[5] 耿明昕,吳健,安翠翠,等.110kV戶(hù)內(nèi)變電站降噪措施及設(shè)計(jì)優(yōu)化研究[J].陜西電力,2013(11):80-85.
[6] 唐嘉.佛山城區(qū)110kV變電站環(huán)境噪聲現(xiàn)狀及治理建議[J].環(huán)境研究與監(jiān)測(cè),2013,26(4):44-50.
[7] Shahbazi B, Savaghebi M,Ashouri M,et al. Investigation of Transformer Cooling Improvement Utilizing Online Monitoring System[C]//3rd IEEE Conference on Industrial Electronic and Applications,2008.
[8] 陳濤,李武興,梁向東,等.35kV變壓器室通風(fēng)系統(tǒng)選型與改造[J].供用電,2009,26(2):52-55.
[9] 陳敏華.地下室變配電房通風(fēng)設(shè)計(jì)[J].中國(guó)科技縱橫,2011(9):270.
[10] 王香麗.地下變電站通風(fēng)空調(diào)系統(tǒng)的節(jié)能性研究[D].上海:東華大學(xué),2012.