真空斷路器開斷并聯(lián)電抗器過電壓試驗研究

來源:電工電氣發(fā)布時間:2016-04-06 14:06 瀏覽次數(shù):17

真空斷路器開斷并聯(lián)電抗器過電壓試驗研究 

劉承勝,陳俊武


華中科技大學(xué) 電氣與電子工程學(xué)院,湖北 武漢 430074 
 

摘 要:針對國內(nèi)35kV與20kV系統(tǒng)真空斷路器開斷并聯(lián)電抗器系統(tǒng)事故多發(fā)情況,開展35kV系統(tǒng)工況下的現(xiàn)場試驗,分析了開斷后的暫態(tài)過程及過電壓的機理,并在實驗室進行了20kV系統(tǒng)真空斷路器在額定電流下投切電抗器的截流試驗,研究截流值和過電壓規(guī)律。結(jié)果表明:截流過電壓幅值遠小于重燃過電壓,多次重燃過電壓是真空斷路器開斷并聯(lián)電抗器頻繁出現(xiàn)高過電壓的主要原因;在系統(tǒng)典型額定工況下,300A負載電流下的截流值比100A負載電流下小,真空斷路器的截流值隨著開斷電流的增大而減小的理論在系統(tǒng)額定電流下同樣成立。
關(guān)鍵詞:真空斷路器;并聯(lián)電抗器;截流;重燃過電壓
中圖分類號:TM472;TM561.2 文獻標識碼:A 文章編號:1007-3175(2014)10-0037-04


Research on Overvoltage Test of Vacuum Circuit Breaker Switching-Off Shunt Reactor 

LIU Cheng-sheng, CHEN Jun-wu 
School of Electrical and Electronic Engineering, Huazhong University of Science and Technology, Wuhan 430074, China 
 

Abstract: As overvoltage failures frequently occur in vacuum circuit breakers switching-off shunt reactors of 35kV or 20kV power system, the field tests were carried out in the operating condition of 35kV power system. This paper analyzed the transient process caused by the opening operation and the overvoltage mechanism.The chopping current test of vacuum circuit breaker switching off shunt reactors was carried out under rated current condition in the laboratory. This paper researched the chopping current value and the overvoltage regulation. The results show that the overvoltage of chopping current is much smaller than multiple reignition overvoltage, and multiple reignition overvoltage is the main reason of overvoltage failures of vacuum circuit breakers switching-off shunt reactors. In the typical conditions of power system, the chopping current of 300A load current is smaller than that of 100A load current. The theory that the chopping current value of vacuum circuit breakers decreases with the increase of breaking current is completely true at rated high current.
            Key words: vacuum circuit breaker; shunt reactor; chopping current; reignition overvoltage


參考文獻
[1] 王季梅.真空開關(guān)技術(shù)與應(yīng)用[M].北京:機械工業(yè)出版社,2008.
[2] 范舜.真空斷路器開斷與關(guān)合不同負載時的操作過電壓[M].北京:中國電力出版社,2000.
[3] 安昌萍.真空斷路器操作過電壓研究[D].重慶:重慶大學(xué),2002.
[4] 關(guān)永剛,唐琦雯,劉衛(wèi)東,等.40.5kV真空斷路器開斷并聯(lián)電抗器時過電壓的產(chǎn)生機制[J].中國電機工程學(xué)報,2012,32(33):124-132.
[5] 杜寧,關(guān)永剛,張景升,等.40.5kV真空斷路器開斷并聯(lián)電抗器的現(xiàn)場試驗[J].清華大學(xué)學(xué)報:自然科學(xué)版,2010,50(4):517-520.
[6] 安昌萍,司馬文霞,廖瑞金,等.35kV真空斷路器開斷空載變壓器時過電壓的研究[J].中國電機工程學(xué)報,2002,22(8):99-103.
[7] 李召家,黎東升.真空斷路器投切并聯(lián)電抗器試驗研究[J].廣東電力,2003,16(4):29-33.
[8] 王季梅.真空開關(guān)的現(xiàn)狀及發(fā)展趨勢[J].電力設(shè)備,2005,6(2):1-5.