電流互感器二次回路阻抗不匹配對差動保護的影響

來源:電工電氣發(fā)布時間:2016-04-06 09:06 瀏覽次數(shù):19

電流互感器二次回路阻抗不匹配對差動保護的影響 

盧慶港1,樂曉蓉2,解軍3

1 蘇州熱工研究院有限公司,江蘇 蘇州 215004;2 蘇州工藝美術職業(yè)技術學院,江蘇 蘇州 215104;3 廣州工程技術職業(yè)學院,廣東 廣州 510925 
 

摘 要:在電動機啟動過程中由于非周期分量及高倍數(shù)電流的綜合作用,當電流互感器(CT) 二次回路阻抗不匹配時,兩側(cè)的二次電流存在差異而形成差流,導致差動保護誤動作。通過對多組錄波數(shù)據(jù)進行分析,重現(xiàn)了不同二次回路阻抗下的差動動作軌跡,并研究了二次回路阻抗不匹配對差動保護的影響,認為只有在設計階段對CT 及二次電纜按照標準進行嚴格計算及選型,保證CT 的暫態(tài)特性滿足工程要求,使差動兩側(cè)CT 的二次負荷盡量平衡,減少可能出現(xiàn)的差電流,才能有效避免此類誤動的發(fā)生。
關鍵詞:電動機;啟動;差動保護;誤動;動作軌跡;二次回路;阻抗;不匹配
中圖分類號:TM452 文獻標識碼:B 文章編號:1007-3175(2014)02-0037-04


Mismatch Impact of Current Transformer Secondary Circuit Impedance on Differential Protection 

LU Qing-gang1, LE Xiao-rong2, XIE Jun3 
1 Suzhou Nuclear Power Research Institute Co., Ltd, Suzhou 215004, China;2 Suzhou Art & Design Technology Institute, Suzhou 215104, China; 3 Guangzhou Institute of Technology, Guangzhou 510925, China 
 

Abstract: In motor starting process, due to the synthetic function of non-cycle component and high times current, secondary currents at both side will form differential current due to existing difference, to cause differential protection unwanted operation when the current transformer (CT)secondary circuit impedance mismatching. Via analysis to multi-groups recorded wave data, the action tracks under different secondary circuit impedance reappeared and this paper researched on mismatch impact of secondary circuit impedance on differential protection, pointing out that only if in design stage the CT and secondary cables were carried out strict calculation and model selection according to standards to ensure transient characteristics of CT to meet engineering requirements, making differential action secondary load of CT at both side in balance as possible and reducing differential current taking place possibly, thus the differential protection would effectively avoid such a kind of unwanted operation.
       Key words: motor; start-up; differential protection; unwanted operation; action track; secondary circuit; impedance; mismatch


參考文獻
[1] GB/T 14285—2006 繼電保護和安全自動裝置技術規(guī)程[S].
[2] 葛懷東,姚斌,秦紅霞. 電動機差動保護誤動事故的分析[J]. 電力設備,2007,8(11):65-67.
[3] 諶爭鳴. 暫態(tài)不平衡電流引起的發(fā)電機差動保護誤動分析[J]. 繼電器,2008,36(10):86-88.
[4] 宋志明,余高旺,邢文,等. 負荷電流下并聯(lián)電抗器差動誤動現(xiàn)象及解決措施[ J ] . 電力系統(tǒng)保護與控制,2011,39(20):145-150.
[5] 王維儉. 電氣主設備繼電保護原理與應用[ M ] .2版. 北京:中國電力出版社,2002.
[6] 朱聲石. 差動保護的暫態(tài)可靠性[J]. 繼電器,2002,30(8):1-5.