互聯(lián)電網(wǎng)一次調(diào)頻特性研究
任麗娜
山西省電子信息產(chǎn)品檢驗(yàn)所,山西 太原 030001
摘 要:介紹了一次調(diào)頻在電力系統(tǒng)中的作用,從原動(dòng)機(jī)參與一次調(diào)頻的角度出發(fā),研究了機(jī)組一次調(diào)頻及其投入狀態(tài)與電網(wǎng)頻率品質(zhì)和聯(lián)絡(luò)線傳輸功率之間的關(guān)系,給出了不同一次調(diào)頻分布下頻率響應(yīng)曲線與聯(lián)絡(luò)線功率變化圖。結(jié)果表明,在合理選擇機(jī)組的調(diào)頻死區(qū)后,當(dāng)各區(qū)域內(nèi)機(jī)組的一次調(diào)頻功能投入均勻時(shí),既可以提高電網(wǎng)頻率的品質(zhì),又可以緩解緊急事故下區(qū)域間互助和聯(lián)絡(luò)線過(guò)載之間的矛盾,改善電網(wǎng)運(yùn)行的安全性和可靠性。
關(guān)鍵詞:一次調(diào)頻;聯(lián)絡(luò)線功率;負(fù)荷擾動(dòng)
中圖分類號(hào):TM712 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1007-3175(2013)12-0026-04
Primary Frequency Characteristics Study of Interconnected Power System
REN Li-na
Shanxi Electronic Information Product Inspection Institute, Taiyuan 030001, China
Abstract: Introduction was made to the function of primary frequency control. Starting from the angle of original machine taking part in primary frequency control, this paper studied the relationship between generators unit primary frequency control and its connecting status and power system quality and tie-line transmission power, giving frequency response curves and tie-line power change diagrams under different primary frequency distribution. The result shows that after the generators unit frequency dead zone is rationally selected, when generators unit primary frequency control function in each area is connected evenly, the quality of power system frequency can be raised, as well as the contradiction between areas mutual assistance and tie-line overload can be released under emergency accident, which improve the safety and reliability of power system operation.
Key words: primary frequency control; tie-line power; load disturbance
參考文獻(xiàn)
[1] 魏慶海,魯順,范東春,陳曉東,李鐵.東北電網(wǎng)頻率與聯(lián)絡(luò)線潮流的關(guān)系[J].電網(wǎng)技術(shù),2004,28(6):22-25.
[2] 張毅明,羅承廉,孟遠(yuǎn)景,何南強(qiáng).河南電網(wǎng)頻率響應(yīng)及機(jī)組一次調(diào)頻問(wèn)題的分析研究[J].中國(guó)電力,2002(7):35-38.