Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 往年索引

斷路器跳位監(jiān)視與防跳回路的分析與改進

來源:電工電氣發(fā)布時間:2016-03-14 10:14 瀏覽次數(shù):8

斷路器跳位監(jiān)視與防跳回路的分析與改進 

葉晴煒

云南省電力設(shè)計院,云南 昆明 650051 
 

摘 要:某變電站252 kV SF6瓷柱式斷路器防跳回路因設(shè)計缺陷使斷路器跳位監(jiān)視回路存在寄生回路,導致操作箱對斷路器的跳位監(jiān)視發(fā)生錯誤。分析了防跳回路對跳位監(jiān)視回路的影響,并對比了550 kV H-GIS斷路器出現(xiàn)的類似問題。闡述了成因和解決方法,對防跳回路的設(shè)計提出了改進,在跳位監(jiān)視回路中串聯(lián)斷路器常閉輔助節(jié)點和就地防跳繼電器的常閉節(jié)點,以解決寄生回路對跳位監(jiān)視的影響。
關(guān)鍵詞:跳位監(jiān)視;防跳回路;斷路器
中圖分類號:TM561.3 文獻標識碼:B 文章編號:1007-3175(2015)02-0032-03


Analysis and Improvement on Open-Position Monitoring and Anti-Pumping Circuit of Circuit Breaker 

YE Qing- wei 
Yunnan Electric Power Design Institute, Kunming 650051, China 
 

Abstract: The anti-pumping circuit of a 252 kV SF6 circuit breaker used in a certain substation existed parasitic circuits in its open-position circuit because of design deficiency, which caused the operation box to make mistakes towards the open-position monitoring of the circuit breaker. This paper analyzed the effect of the anti-pumping circuit on the open-position monitoring circuit, and compared with a similar phenomenon that happened to the 550 kV H-GIS circuit breaker. The factor and solution has been explained, and it has also proposed improvement towards the design of the anti-pumping circuit. In the open-position monitoring circuit, the normally closed auxiliary nodal point of the circuit breaker was connected in series to the normally closed nodal point in in-site anti-pumping relay of the circuit breaker to remove the effect of parasitic circuits on open-position monitoring.
Key words: open-position monitoring; anti-pumping circuit; circuit breaker


參考文獻
[1] 高山,卞超.斷路器防跳回路缺陷分析[J].高壓開關(guān),2007,24(3):35-37.