凝露對變頻器的影響分析及預防措施

來源:電工電氣發(fā)布時間:2016-03-14 10:14 瀏覽次數(shù):11

凝露對變頻器的影響分析及預防措施 

孫海軍

浙江大唐烏沙山發(fā)電有限責任公司,浙江 寧波 315722 
 

摘 要:針對某沿海電廠一起變頻器整流單元短路故障事故,分析得出母線銅排凝露的產生是引起本次變頻器短路的主要原因,討論了凝露對變頻器的影響機理,給出了預防凝露的措施,指出只要保持變頻器柜體內部溫度始終高于外部環(huán)境溫度,即可防止變頻器柜體內部發(fā)生凝露,降低突發(fā)事故風險。
關鍵詞:凝露;變頻器;故障;預防措施
中圖分類號:TN773 文獻標識碼:A 文章編號:1007-3175(2015)02-0035-03


Analysis and Precaution of Condensation Effects on Inverter 

SUN Hai-jun 
Zhejiang Datang Wushashan Power Co., Ltd, Ningbo 315722, China 
 

Abstract: Based on the short-circuit fault accident of a inverter rectifier unit in a coastal power plant, this paper analyzed that the condensation generated by bus bar copper bar was the main reason to cause inverter short circuit this time, and discussed the condensation influence mechanism to inverter, providing measures to prevent condensation. It is pointed out that the inverter cabinet internal condensation would be prevented, only if the internal temperature of inverter cabinet is kept higher than external environment temperature, which will reduce the accident risk.
Key words: condensation; inverter; failure; precautions