特高壓變電站隔離刀閘二次回路若干問題分析及改進

來源:電工電氣發(fā)布時間:2020-10-23 16:23 瀏覽次數(shù):714
特高壓變電站隔離刀閘二次回路若干問題分析及改進
 
劉濤,裴東良,楊征,王卓,田蕊
(國網河南省電力公司檢修公司,河南 鄭州 450051)
 
    摘 要:針對超(特)高壓變電站和換流站隔離、接地刀閘設備暴露出的問題及缺陷,總結了刀閘二次回路若干問題并提出改進措施。為防止電機電流串入控制回路而燒損元器件,刀閘控制回路宜與電機回路電源獨立;氣體封閉絕緣組合電器(GIS)間隔整流器出口宜設置平衡電阻橋接地,以便于維護檢修工作;刀閘輔助接點不宜閉鎖斷路器合閘,以確保斷路器合閘控制回路的可靠性;針對長期帶電的電子式熱繼電器易燒損,接有長電纜的刀閘電機接觸器易發(fā)生誤動事故,提出了電源接線等改進方案;指出測控裝置出口繼電器接點性質應與控制回路電源性質一致,并針對GIS間隔溫濕度控制器與加熱器分散布置的缺點給出改進意見。為刀閘設備的生產制造、系統(tǒng)設計和現(xiàn)場運維檢修工作提供了參考。
    關鍵詞:超(特)高壓變電站;隔離刀閘;接地刀閘;控制回路;平衡電阻橋;電子式熱繼電器
    中圖分類號:TM564;TM63     文獻標識碼:B     文章編號:1007-3175(2020)10-0032-07
 
Analysis and Improvement on Problems in Secondary Circuit of Disconnector in UHV Substations
 
LIU Tao, PEI Dong-liang, YANG Zheng, WANG Zhuo, TIAN Rui
(Maintenance Company of Henan Electric Power Corporation, Zhengzhou 450051, China)
 
    Abstract: For the problems of disconnector and earthing switches in EHV (UHV) substation and converter station, this paper summarizes some problems in the secondary circuit of switches and puts forward improvement measures. In order to prevent the motor current flow in series to the control circuit and burn the components, the switches control circuit and motor circuit should be seperately power supplied. The earthing balance resistance bridge should be installed at the outlet of GIS unit’s rectifier to facilitate maintenance and repair work. To ensure the reliability of circuit breaker closing control circuit, the auxiliary contact of switches should not block the closing operation of circuit breaker. For the long-term electrified electronic thermal relay is frequently burnt, and the switches motor contactor connected with long cable is easy to wrong operation, the power wiring and other improvement schemes are proposed. The nature of outlet relay contacts should be consistent with that of control circuit power supply. Disadvantage and suggestion of decentralized arrangement of GIS unit’s temperature & humidity controller and its heater is put forward. It provides a reference for the manufacture, system design and on-site operation and maintenance of switchgear.
    Key words: EHV(UHV) substation; disconnector; earthing switch; control circuit; balanced resistance bridge; electronic thermal relay
 
參考文獻
[1] 張書琴,張克選,高延峰,等. GIS現(xiàn)場驗收及運行中若干問題的研究[J]. 高壓電器,2017,53(5):193-199.
[2] 劉濤,裴東良,徐瑞娜,等.1 000 kV HGIS隔離/ 接地刀閘控制觸點頻繁燒損事故分析及改進[J]. 華北電力技術,2017(5):60-65.
[3] 劉濤,李鳳旭,楊光,等. 直流不接地系統(tǒng)臨時接地裝置在特高壓南陽變電站的應用[J]. 電氣應用,2015,34(1):116-119.
[4] 李茹勤,劉濤,張高峰,等. 整流器出口設置平衡電阻橋接地方案的研究[J]. 東北電力技術,2018,39(7):18-21.
[5] 李煒,劉明光,田浩,等. 隔離開關傳動機構的誤差分析與研究[J]. 高壓電器,2018,54(3):32-36.
[6] 劉濤,王貴山,黃健金,等.500 kV斷路器合閘回路故障引起的保護誤動事故分析[J]. 陜西電力,2014,42(6):77-80.
[7] 梁方建,吳建輝,胡路東,等. 一起220 kV隔離開關電機開關誤分事故分析[J]. 高壓電器,2018,54(1):249-251.
[8] 雷興,潘學萍,孫彬,等. 電纜分布電容對出口繼電器動作的影響分析及應對措施[J]. 電力系統(tǒng)自動化,2017,41(15):170-175.
[9] 馮順, 曲欣, 王毅, 等. 一起刀開關誤動作引起500 kV線路跳閘的分析[J]. 電氣應用,2018,37(9):54-57.
[10] 孟恒信. 出口繼電器安全動作功率分析[J]. 電力系統(tǒng)自動化,2009,33(6):104-107.