Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 往年索引

一起集合式電容器差壓保護動作后解體分析

來源:電工電氣發(fā)布時間:2018-03-19 14:19 瀏覽次數(shù):658
一起集合式電容器差壓保護動作后解體分析
 
鄭隆,申濤
(國網(wǎng)浙江省電力公司檢修分公司,浙江 杭州 310009)
 
    摘 要:對一起差壓保護動作后的集合式電容器進行電氣和油化試驗分析,并對其本體進行拆解和研究,找出故障是由于安裝過程中的錯誤接線,導致導線過熱逐漸熔斷,造成一次有差電壓,保護跳閘。分析了差壓保護的動作情況,對該類故障的查找提出建議,供廠家和運維檢修單位參考。
    關(guān)鍵詞:集合式;電容器;差壓保護;故障分析
    中圖分類號:TM531     文獻標識碼:A     文章編號:1007-3175(2018)03-0047-03
 
Causes Analysis of an Assembling Capacitor Differential Pressure Protection Action
 
ZHENG Long, SHEN Tao
(Maintenance Branch Company of State Grid Zhejiang Electric Power Corporation, Hangzhou 310009, China)
 
    Abstract: After differential pressure protection action, this paper analyzed the electrical and oil tests of the assembled capacitors, and dismantled and studied on its noumenon. The fault was due to the false wiring in the installation process, so as to lead to the wire overheating and gradually fusing, which caused the primary differential pressure and protection tripping. Analysis was made to the action condition of differential pressure protection. This paper gave suggestions of searching this type of faults to provide references for manufacturers and maintenance personnel.
    Key words: assembling; capacitor; differential pressure protection; accident analysis
 
參考文獻
[1] 戴軍瑛. 一起集合式并聯(lián)電容器故障分析[J]. 浙江電力,2007,26(5):74-75.
[2] 王云杰,王洪寅,王虎,等. 集合式電容器差壓保護動作原因分析[J]. 電工電氣,2012(11):42-44.
[3] 丁國成,李偉,王來善,等. 一起10 kV集合式電容器保護頻繁動作原因分析[J]. 電力電容器與無功補償,2010,31(5):67-70.